Types of ExtinguishersThere are two main types of fire extinguishers: Stored pressure and generated pressure. In stored pressure units, the expellant is stored in the same chamber as the firefighting agent itself. Depending on the agent used, different propellants are used. With dry chemical extinguishers, nitrogen is typically used; water and foam are pressurized with air. Stored pressure are the most common type fire extinguishers. Generated pressure, or cartridge-operated extinguishers, contain the expellant gas in a separate cartridge that is punctured prior to discharge, exposing the propellant to the agent. These types as are not common, used primarily in areas such as industrial facilities, where they receive higher-than-average use. They have the advantage of simple and prompt recharge, allowing an operator to discharge the extinguisher, recharge it, and return to the fire in an reasonable amount of time. Unlike stored pressure types, these extinguishers utilize compressed carbon dioxide instead of nitrogen. Fire extinguishers are further divided into handheld and cart-mounted, also called wheeled extinguishers. Handheld extinguishers weight from 2 to 30 pounds (1 to 14 kilograms), and are hence easily portable by hand. They exist in both stored- and generated-pressure types and contain all types of suppressants. Cart-mounted units typically weigh 50+ pounds (23+ kilograms), are cartridge-operated, and typically contain either dry chemical, Purple-K, foam, Halon, or CO2. Wheeled models are most commonly found at construction sites, airport runways, heliports, and temporary landing sites. HistoryThe first automatic fire extinguisher of which there is any record was patented in England in 1723 by Ambrose Godfrey, a celebrated chemist. It consisted of a cask of fire-extinguishing liquid containing a pewter chamber of gunpowder. This was connected with a system of fuses which were ignited, exploding the gunpowder and scattering the solution. This device was probably used to a limited extent, as Bradley's Weekly Messenger for November 7, 1729, refers to its efficiency in stopping a fire in London. The modern fire extinguisher was invented by British Captain George William Manby in 1818; it consisted of a copper vessel of 3 gallons (13.6 litres) of pearl ash (potassium carbonate) solution contained within compressed air. The soda-acid extinguisher was invented in 1881 by Almon M. Granger. His extinguisher used the reaction between sodium bicarbonate solution and sulfuric acid to expel pressurized water onto a fire.[1] A vial was suspended in the cylinder containing concentrated sulfuric acid. Depending on the type of extinguisher, the vial of acid could be broken in one of two ways. One used a plunger to break the acid vial, while the second released a lead bung that held the vial closed. Once the acid was mixed with the bicarbonate solution, carbon dioxide gas was expelled and thereby pressurize the water. The pressurized water was forced from the canister through a nozzle or short length of hose. Around 1912 Pyrene invented the carbon tetrachloride (CTC) extinguisher, which expelled the liquid from a brass or chrome container by a handpump; it was usually of 1 imperial quart (1.1 L) or 1 imperial pint (0.6 L) capacity but was also available in up to 2 imperial gallon (9 L) size. A further variety consisted of a glass bottle "bomb" filled with the liquid that was intended to be hurled at the base of a fire. The CTC vaporized and extinguished the flames by chemical reaction. The extinguisher was suitable for liquid and electrical fires, and was popular in motor vehicles for the next 60 years. In the 1940s, Germany invented the liquid chlorobromomethane (CBM) for use in aircraft. It was more effective and slightly less toxic than carbon tetrachloride and was used until 1969. Methyl Bromide was discovered as an extinguishing agent in the 1920s and was used extensively in Europe. It is a low-pressure gas that works by inhibiting the chain reaction of the fire and is the most toxic of the vaporizing liquids, used until the 1960s. The vapor and combustion by-products of all vaporizing liquids were highly toxic, and could cause death in confined spaces. ClassificationInternationally there are several accepted classification methods for hand-held fire extinguishers. Each classification is useful in fighting fires with a particular group of fuel. Australia
In Australia, yellow (Halon) fire extinguishers are illegal to own or use on a fire, unless an essential use exemption has been granted.[2] United KingdomAccording to the standard BS EN 3, fire extinguishers in the United Kingdom as all throughout Europe are red RAL 3000, and a band or circle of a second color covering at least 5% of the surface area of the extinguisher indicates the contents. Before 1997, the entire body of the fire extinguisher was color coded according to the type of extinguishing agent.
The UK recognizes six fire classes. Class A fires involve organic solids such as paper and wood. Class B fires involve flammable liquids. Class C fires involve flammable gases. Class D fires involve metals, Class E fires involve live electrical items and Class F fires involve cooking fat and oil. Fire extinguishing capacity is rated by fire class using numbers and letters such as 13A, 55B. EN 3 does not recognize a separate E class - this is an additional feature requiring special testing (dielectric test per EN 3-7:2004) and NOT passing this test makes it compulsory to add a special label (pictogram) indicating the inability to isolate the user from a live electric source. In the UK the use of Halon gas is now illegal except under certain situations.[3] United StatesThere is no official standard in the United States for the color of fire extinguishers, though they are typically red, except for Class D extinguishers, which are usually yellow, and water, which usually silver, or white if water mist. Extinguishers are marked with pictograms depicting the types of fires that the extinguisher is approved to fight. In the past, extinguishers were marked with colored geometric symbols, and some extinguishers still use both symbols. No official pictogram exists for Class D extinguishers, though training manuals sometimes show a drill press with shavings burning underneath. The types of fires and additional standards are described in NFPA 10: Standard for Portable Fire Extinguishers.
The Underwriters Laboratories rate fire extinguishing capacity in accordance with UL/ANSI 711: Rating and Fire Testing of Fire Extinguishers. The ratings are described using numbers preceding the class letter, such as 1-A:10-B:C. The number preceding the A multiplied by 1.25 gives the equivalent extinguishing capability in gallons of water. The number preceding the B indicates the size of fire in square feet that an ordinary user should be able to extinguish. There is no additional rating for class C, as it only indicates that the extinguishing agent will not conduct electricity, and an extinguisher will never have a rating of just C.
InstallationFire extinguishers are typically fitted in buildings at an easily-accessible location, such as against a wall in a high-traffic area. They are also often fitted to motor vehicles, watercraft, and aircraft - this is required by law in many jurisdictions, for identified classes of vehicles. Under NFPA 10 all commercial vehicles must carry at least one fire extinguisher (size/UL rating depending on type of vehicle and cargo (ie. fuel tankers typically must have a 9.1 kg (20 lb). when most others can carry a 2.3 kg (5 lb).) The revised NFPA 10 created criteria on the placement of "Fast Flow Extinguishers" in locations such as those storing and transporting pressurized flammable liquids and pressurized flammable gas or areas with possibility of three dimensional class B hazards are required to have "fast flow" extinguishers as required by NFPA 5.5.1.1. Varying classes of competition vehicles require fire extinguishing systems, the simplest requirements being a 1A10BC handheld portable extinguisher mounted to the interior of the vehicle. Types of extinguishing agentsDry Chemical (lyophobic colloid)Powder based agent that extinguishes by separating the four parts of the fire tetrahedron. It prevents the chemical reaction between heat, fuel and oxygen, thus extinguishing the fire.
Foams (lyophilic colloid)Applied to fuel fires as either an aspirated (mixed & expanded with air in a branch pipe) or non aspirated form to form a frothy blanket or seal over the fuel, preventing oxygen reaching it. Unlike powder, foam can be used to progressively extinguish fires without flashback.
WaterCools burning material.
Water Additives
Clean AgentsAgent does not extinguish by smothering, but displaces oxygen, or inhibits chemical chain reaction. They are labeled clean agents because they do not leave any residue after discharge which is ideal for sensitive electronics and documents.
Class D
MaintenanceMost countries in the world require regular fire extinguisher maintenance by a competent person to operate safely and effectively, as part of fire safety legislation. Lack of maintenance can lead to an extinguisher not discharging when required, or rupturing when pressurized. Deaths have occurred, even in recent times, from corroded extinguishers exploding. There is no all-encompassing fire code in the United States. Generally, most municipalities (by adoption of the International Fire Code) require inspections every 30 days to ensure the unit is pressurized and unobstructed (done by an employee of the facility) and an annual inspection by a qualified technician. Hydrostatic pressure testing for all types of extinguishers is also required, generally every five years for water and CO2 models up to every 12 years for dry chemical models. Recently the National Fire Protection Association and ICC voted to allow for the elimination of the 30 day inspection requirement so long as the fire extinguisher is monitored electronically. According to NFPA, the system must provide record keeping in the form of an electronic event log at the control panel. The system must also constantly monitor an extinguisher’s physical presence, internal pressure and whether an obstruction exists that could prevent ready access. In the event that any of the above conditions are found, the system must send an alert to officials so they can immediately rectify the situation. Electronic monitoring can be wired or wireless. In the UK, three types of maintenance are required:
Fire extinguisher signs
Heavy-duty CO2-powered fire extinguisher on standby at a temporary helicopter landing site
Fire extinguisher identification signs are small signs designed to be mounted near a fire extinguisher, in order to draw attention to the extinguisher's location (Ex. If the Extinguisher is on a large pole the sign would generally be at the top of the pole so it can be seen from a distance) Such signs may be manufactured from a variety of materials, commonly self-adhesive vinyl, rigid PVC and aluminum. In addition to words and pictographs indicating the presence of a fire extinguisher , modern extinguisher ID signs also describe the extinguishing agent in the unit, and summarize the types of fire on which it may safely be used. Public and government buildings are often required, by local legal codes, to provide an ID sign for each extinguisher on the site.[5] Similar signs are available for other fire equipment (including fire blankets and fire hose reels), and for other emergency equipment (such as first aid kits). Placement of fire extinguisher signsFire extinguisher signs are mounted above or to the side of the extinguisher they relate to. Most licensing authorities have regulations describing the standard appearance of these signs (e.g. text height, pictographs used and so on)[6]. Photo-luminescent fire extinguisher signsPhoto-luminescent fire extinguisher signs are made of a polymer that absorbs ambient light and releases it slowly in dark conditions - the sign "glows in the dark". Such signs are independent of an external power supply, and so offer a low-cost, reliable means of indicating the position of emergency equipment in dark or smoky conditions. Photo-luminescent signs are sometimes mis-described as being reflective. A reflective material will only return ambient light for as long as the light source is supplied, rather than storing energy and releasing it over a period of time. However, many fire extinguishers and extinguisher mounting posts have strips of reflective adhesive tape placed on them to facilitate their location in situations where only emergency lighting or flashlights are available. Older luminescent signs sometimes used a radioactive tritium source to energise the polymeric material. This source could pose a hazard when such signs are dismantled or damaged[7]. Modern photoluminescent materials are, however, not radioactive. References
Automatic Sprinkler Protection - Goram Dana, S.B. External linksWikimedia Commons has media related to:
| | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||